E. Dold & Söhne

www.dold.com

NMT
NMT slave
Error control
Node guarding,
Life guarding
Boot-up
No
Node ID
Hardware switch
No. of PDO
RPDOs
1
TPDOs
No
PDO modes
Event-triggered,
Synchronous (cyclic),
Synchronous (acyclic)
PDO linking
No
PDO mapping
Variable
No. of SDO
Server
1
Client
1
Emergency message
Emergency producer
Sync
No
Sync producer:
No
Sync counter:
Time stamp
No
Additional functions
None
Supported application layer
CiA 301 V 3.0
Supported frameworks
None
Supported profiles
CiA 401: CANopen device profile for generic I/O modules
Certified
No

Headquarters

E. Dold & Söhne KG
Bregstr. 18
DE-78120 Furtwangen

Phone: +49-7723-6540
Fax: +49-7723-654356
Email: dold-relays@dold.com
URL : www.dold.com

IL 5507 analog output module

Availability
In stock
Analog output module for CANopen IL 5507.
  • Installation in consumer units for building automation or industrial cabinets
  • Space saving, two analog outputs at a width of 35 mm space required similar to two standard line circuit breakers
  • 2 × analog output, available for 2 × 0 V to 10 V,
    2 × 0 mA to 20 mA,
    2 × –10 V to +10 V or
    2 × 4 mA to 20 mA
  • 12-bit resolution allows accuracy of less than ±0,1 %
  • Outputs with galvanic separation to bus and power supply as standard provide high interference resistance
  • No external supply necessary for output signal
  • Can be used in all CANopen networks because of high data transmission rate up to 1 Mbit/s
  • Free configuration software, CoDeSys
  • According to IEC/EN 61131-2
  • CANopen-Interface according to CiA 301 V 3.0, CiA 401
  • LED indication for power supply and bus activity

The analog output module IL 5507 for CANopen generates analog signals e.g. to control inverters, power and servo controls. It is designed in a compact enclosure that can be installed in consumer units for building automation as well as in industrial cabinets.

Accessories:

  • CANopen PLC IL 5504, DX 5504 (IP67)
  • I/O module IN 5509
  • Input module, analog/digital DX 5509, IP 5502, IL 5508
  • Output module IP 5503